When technician arrived the home was warm and the air conditioner was not working. So the Technician went into the attic and found the main 60 amp breaker was in the off position, so the technician checked for loose wires also checked for motor to be shorted out. Please note the breaker was off not tripped, I turned the breaker on checked volts, amps, temperature splits, refrigerant pressures including superheat and subcool, checked contactor, and the capacitor, checked the blower wheel, drains, filter, and duct pressures. I rechecked the blower motor after running for a while its drawimg 2.2 amps and the 15 mfd capacitor tested at 15.1 system is working ok at this time. Homeowner is using there free tune up for this visit.