2014 4t closet upflow hp. Wetswitch was not in the proper place, heavy water on the floor of return would have tripped anyways. UV bulb is out. Filter was soaked. Drain was blocked - cleared, homeowner took it upon himself to attach vacuum to the port outside and I poured water in primary pan. Evaporator coil has detectable refrigerant leaks, also a history of freezing. Blower wheel has heavy buildup. Heatstrips come on when set to heat instantly indicating HP refrigerant issues. Compressor inrush amperage exceeds manufacturers specifications. Start capacitor is blown. Run capacitor is failing. Primary electrical control contractor is buzzing when pulled in. Homeowner was with me most of the time so I decided to educate on how the system is performing, hazards and general reliability. I was able to get confirmation from parts that the evaporator coil is no longer available. Homeowner agreed, after sitting down and reviewing all video/photo evidences to speak to a CA today 1/29