Came out for an evaluation outdoor unit was not running due to trip core sensor found a snake wrapped around the shaft of the fan motor removed the snake reset the core sensor and monitored all pressures and amp draw over the course of 30 minutes my findings indicated that the TXV is failing and causing the coils to freeze up which in turn causes liquid to slug back to the compressor raises temperature and head pressure fan motor amp draw was also increasing over this duration indicating that it is compromised and likely to fail again presented homeowner with options and applied for financing however unfortunately she was denied financing we will email her the estimates and invoice allowing her some time to discuss these options with her brother co-owner of the home and then she can call us back