Kellen M.

Kellen M.


Job Checkin

2019 5t attic horizontal hp. Drain line clear. Filter - homeowner placed it backwards - fixed. Evaporator coil has signs of dust build up on the top side of evaporator coil on the intake side. Blower - heavy biological growth present on the blower door, hub, wiring and wheel - this compromises indoor air quality and reduces optimal airflow and increases external static pressure. Passthrough breakers are getting hit with heavy humidity which is developing rust on the line side of high voltage. No saftey float switch on condensate primary line - increased risk of unwanted flooding of the system. Condenser coils washed. 70/10 mfd capacitor below manufacturer tolerance. Compressor inrush amperage exceeds manufacturer specifications. Refrigerant charge acceptable. Defrost control board functional. Shared all information with homeowner. Homeowners claim they are moving and will consider the estimates built to restore the system. Declined work at this time. This protects the technician due