51 Koweba Lane
Indianapolis, IN 46201
(855) 932-6437

Our Top Cities


Job Locations
for cicero, il


Map of Cicero IL
Sequoiah B.

Sequoiah B.


Job Checkin

Portable Extinguishers, Emergency / Exit Lights, and Kitchen Suppression Inspection 5: FP Annual 12: FP Annual Ansul R102 3 gal: FP Semi Annual Inoperable Deficiency: Ansul system is red tagged and needs repairs done now!!!!!!! Parts needed are,3 gal ansulex,101-30 cartridge, hose, bursting disc, 4x scissors, 1x 3 gal stainless tank hydro tested, and regulator tested, also needs 1x G2-301 emergency light, 3x 4.5 ah battery’s. Labor est is about 3x hours. Deficiency for 12: Exit light by back door and emergency lights by back door and cash register failed inspection and Need replaced Need 2 G2-301 emergency lights 1 G1-101 exit light