Kitchen Suppression, Portable Extinguishers, and Emergency / Exit Lights Inspection FP Semi-Annual FP Annual FP Annual Deficiency: Protex 4600 system is past due for hydrotest 2011. Both duct nozzles are 1h and should be 1L nozzles. Range is only protected by 2 nozzles and should have 3 nozzles per the manufacture specs need to add one 2L nozzle. Detection line is not centered in duct per the manufacture specs line will need to fixed to be in spec. Parts needed Hydrotested protex 4600 tank 2-1L nozzles 1-2L nozzle Cable and conduit for detection line fix.