Kitchen Suppression Inspection Ansul R102 6 gal: FP Semi-Annual Amerex Kp Kp275: FP Annual Ansul R102 3 gal: FP Semi Annual Deficiency for Amerex Kp Kp275: Appliances under hood are to big for hood and stick out. 6 burner range and char are not protected properly. Will need to take out oven or go to a smaller appliance to fit under hood. Amerex hood system Kp275 tank 2012 due for hydrotest. 3 holes on left end of hood need plugged. Needs stove nozzle added Needs pressure relief added Hood is schedule 1 and should be schedule 2