for this job I did a cooling tuneup. everything was to code on the indoor unit. Delta looked fine. At the outdoor unit pressure and temperature on refrigerant was good. Capacitor was in tolerance. In rush was about 20amps higher than suggested LRA. Recommended a hard start or soft start kit. Homeowner declined cleaned out the condenser and unit was running when I left.