On arrival indoor unit was not sending high voltage to the board and was essentially inert. I taped down the door switch and it stayed on but door switch is likely failing. Ecobee thermostat was not sending call for cooling. Wired power and cooling directly and had a call for cooling at furnace and condenser. Once I put wires back in and ecobee on system sent 24 volts call to furnace and condenser. At condenser found disconnect burnt up and not passing power. Once replaced system resumed cooling. Thanks for choosing comfort experts and have a great day.