Performed evaluation Upon arrival indoor unit was functional Outdoor fan motor was running, but compressor was not running Found Capacitor rating at 0MFD Primary electrical control unit has gashing and small metal chunks pulled off of contact terminals System performs with 137.4 starting amperage Replaced capacitor/primary electrical control unit and installed Micro air soft start System amperage draw from 137.4 to 20.4 Amps System delta 18 - replaced filter System left on cool at exit