2012 3t hp pancake. As the system continued to get worse from my visit in February 2024, even then setting a CA appointment... This time, homeowner stated $400+ electric bills and noise coming from condenser. My diagnostic determined- Compressor inrush amps exceed manufacturers specifications. Almost 200° vapor line in heat mode. Minimal refrigerant available for compressor to function correctly. Scorched primary electrical control contractor. Heat spot on defrost control board. Leaks detected in evaporator coil. Homeowner claims headaches and dizziness have occured lately and may be a symptom of refrigerant hazard. Homeowner does not want to throw parts at it anymore and agreed to visit with a CA 1/17/25 @5-7p Homeowner asked why we haven't been out a second time in 2024 and was pretty upset about that; to de-escalate I said we can waive today's service fee all things considered. I went through the history of calls with her to remind of the activities that have taken plac