Upon arrival techs were shown to the air handler as well as the condenser. Techs started with the condenser we got our amp draws as well and the inrush amps the inrush amps was at 144. And the running amps on the compressor was at 10. The running amps on the fan motor was 1.5. The capacitor and contractor both gave good readings and looked good. Once done with the readings techs took the top of the condenser and washed the unit and waxed the unit. Then tech hooked up the gages and went inside tech started with the deltas the return was at 71 and the supply was at 61. The blower was in good condition. The evaporator coil was also clean everything was working properly. The blower motor was an ecm and we had a txv. Techs suggested a compressor saver to help with the high inrush amps.