Justin  P.

Justin P.


Job Checkin

2020 Goodman Gas Furnace Checked and tightened all electrical connections Changed Customer provided filter, filter is too small needs bigger size Drain was clear and draining Blower motor and wheel were acceptable Evaporator coil was acceptable Supply plenum has slight biological growth build up 2020 Goodman Straight Cool Breaker at main panel was off upon arrival Checked and tightened all electrical connections Dual run capacitor is weak 45/5 reading 22/4.7 Primary electrical unit was acceptable Refrigerant levels are slightly low at this time Fan blades and motor were acceptable Condenser coil was acceptable Washed Condenser coil from inside out Cleared debris out of unit Waxed top of unit Recommended Uv system for biological growth inside system, Dual run cap, compressor saver and HBPPlan Installed compressor saver and auxiliary motor starter