For this evaluation the customer's indoor system was running however the condenser was not because the dual run capacitor was dead. Replace that capacitor under warranty and talked to the customers about installing a hard start kit to keep amp draws low as well as extend the life of the capacitor. We installed the hard start kit and it lowered the inrush amp draw from 147 amps to 99 amps. System was cooling blowing out at 51°.