For this super tune-up I inspected the customers zoned air handler and condenser. For the most part all equipment was measuring within manufacturer's specs and running well with the exception of the compressor over amping on startup. The contactor was buzzing and pitted so I recommended to the customer replacing both the contactor as well as installing a hard start kit to reduce the amp draw on startup to the compressor. The customers wanted to go ahead and get those components fixed which I did and after installing the hard start kit, the compressor went from 172 amps to 96 amps on startup.