Job Checkin

Outdoor was tripped on high pressure lockout. Reset system and checked pressures. Pressures were showing low at this time, indoor air is bypassing Evaporator coil through linser hole and the airhandler door not making proper contact with unit. Per Mark W I will be back tomorrow first call if possible to get equipment to seal the door and linset hole. Under workmanship per Mark W Sealed all air leaks on airhandler door and got Refrigerant charge to correct levels. System is running as should upon leaving