On this cooling tune up I washed and clean condensor coil filter was clean. Superheat 20 ° Subcool 12° Primary drain has issue water is building up in emergency pan because of it. Em pan is rusted out and needs to be replaced Air conditioner cycles are normal All motors test intolerance along with capacitors. All electrical connections are tight Thermostat is clean but maybe need to be replaced. Thermostat doesn't display desired temp very well Adjustents to blower components are not needed. High speed for cooling medium high for heating Recommendations 1.The system could use a soft start device to tackle high in rush. 2. Replace emergency pan 3. Clear drain properly Please be thinking about system replacement. Air conditioners can usually be repaired but isn't always the best options take the time to consider what's best for you and your family. Thanks