1412 Greenwood Road
Weatherford, TX 76008
817-596-4808

Our Top Cities


Job Locations
for keller, tx


Map of Keller TX
wade.gordzelik@acgenius.com

wade.gordzelik@acgenius.com


Job Checkin

For this job the customers downstairs system was tripping the breaker because the compressor was over amping on startup pulling 115 amps with a maximum amp draw of 95, Additionally the Run load amperage on the system was 17.7 with a Max RLA of 16.5. What this means that compressor is working extremely hard and essentially overheating while running causing the system to shut down. I spoke to the customer about his options and being that the system is 27 years old and R- 22 refrigerant the finding a new compressor would be hard and the wait time could be weeks if not months to get the new compressor in and able to be installed. Customer wanted to speak with a comfort advisor about system replacement and it is scheduled for today 11 July at 5:00 p.m.