For this evaluation customers upstairs run capacitor for compressor had failed once again for the third time in less than a year, the start kit was reading 218 MFD however the capacitor was only reading 16 MFD. The original capacitor before I replace it last time was a 50 microfarad however when I looked at the compressor it was calling for a 35 run capacitor. I replaced the 50 with a 35 and after doing so the system kicked on. Again tightened all the high voltage connections and the Spade connections on the capacitor to hopefully prevent the same issue from recurring.