Tech arrived at a membership service call. Upon inspection, the furnace was giving codes for limit switch. The system was reset and reached complete ignition however the blower motor did not come on. The capacitor was tested and out of tolerance. The motor was emanating heat. The ignition components were scorched. The inducer motor was pulling very high amperage. The coil and blower area was dirty. The customer was informed of recommendations today. Due to age, condition, presence of R22 and price of repairs; it is recommended that the customer speak with a Comfort Advisor about upgrading to something more reliable with warranties behind it. The customer agreed and the meeting is set for Friday afternoon 3-5.