Job Checkin

Performed evaluation Upon arrival system was operational There were 3 additional filters inside return grates aswell with April air kit in system return The 3 filters had high build up blocking airflow across system causing coil to freeze - at the end of the supply on bottom there is a bypass to return that has water inside the duct insulation - no standing water inside ducts - no standing water inside coil pan and water is flowing through PVC lines Reccomended Service to IAQ to evaluate homeowner duct work concerns System refrigerant is good Dual run capacitor was out of tolerance compressor 21.24 of 70 Compressor was in and out of operation - while inside attic space compressor had turned off with condensor fan operational Installed dual run capacitor Homeowner joined home and budget protection plan System left on cool at exit