Technician arrived to customers home, asked a couple of questions and then handed the home questioneer. Technician started on the furnace on attic. Insulation level r30, filter was changed, plenums looked I'm clean and good condition, blower wheel in clean condition, drain lines where clear no visible clog, evaporator coil in clean condition, electrical readings in range aswell as wires, drain lines where clear no visible blockage of any kind. Technician then continued to move to the condenser unit on side of home. Cleaned coils in and out, waxed units shell, refrigerant levels in range, capacitor was bad reading 29 on a 35/5, swapped it out with a new 35/5, contactor in good condition. -5/21/25 swapped out capacitor under p&l warranty, was reading 29 swapped it out with a new 35/5.