For this evaluation the customer system was not cooling again, the furnace was blowing air however the condenser was not turning on. Initially when I showed up the customer had the system turned off at the thermostat and when I turned it back on everything started up and was cooling like it was supposed to. The system was showing Previous faults of "Open Fuse", "Short Cycling" and then after multiple times cycling the system on and off again "High Pressure Cut Off Trip" appeared. When I gauged up however my high side prerwas steady around 340 psi or 104⁰F, nowhere near high head pressure. The blower was set to the highest speed and the filter was also clean, additionally the condenser was not very dirty at all. The system had a 7⁰ subcool and a 14⁰ superheat. I poured 2 gallons of water down the primary drain line just to make sure that it wasn't a drain line issue or the float switch. Unfortunately I was unable to replicate the issue however I went ahead and bypassed the high pressure