On arrival the compressor would not turn on. I quickly found the burnt wire to the contactor causing this. Thr indoor unit had a clean coil and blower and clear drain lines. The outdoor unit passed all electrical testing and once I installed a compressor saver kit it started under the 109 LRA at 94 amps. As I left the system was on and heating.