IAQ dehumidification estimate Humidity measured at ~50% Coil drain pan is not leveled correctly so not all water drains out It appears water has overflowed the pan in the past as water staining is present in the supply plenum and will eventually result in biological growth ReLevel the coil or system and install a UV filtration upgrade eliminate these issues Superheat is measuring at 34 which indicates that the TXV is not operating correctly and need to be replaced. TXV issue is resulting in a higher than normal coil operating temperature which is preventing it from condensing as much water from the air as designed No water safeties are present on the equipment as well Homeowners will discuss our findings and get back to us with their decision