On arrival system running and cooling producing 20 degrees delta. Indoor unit clean and in good condition. Outdoor units dual run capicator was out of tolerance and compressor overamping on start up. Replaced dual run with customers permission. Once replaced compressor went from pulling 90 amps to 79 amps on start up and is rated up to 72 amps on start up. Recommended adding a compressor saver kit next year. System cooling as I left.