Job Checkin

5/31/25 When we arrived the homeowner said he shutoff the system because water was leaking through his ceiling. Nathaniel and Aaron went into the attic and flushed a gallon of water through the primary and secondary drain, checked drain pan for cracked pan also checked duct pressures and temp splits, checked refrigerant pressures including superheat and subcool. The secondary drain did not have water in it and was letting air back in causing the primary drain to not drain backing water up into blower area. Filled both traps cycled on system for an hour and rechecked, unit is working good at this time. Previous spots of water are dry in the system, I do not see any visable damage from the water. We will come back Monday and double check install again. 6/2 Aaron checked back and went into the attic and checked the sheetrock it was all dry so I moved insulation back around. Hooked up gauges checked refrigerant pressures including superheat and subcool and added 16 Oz of Refrigerant to