Upon arrival for evaluation system was operational when I got to the home. I still went ahead and did the evaluation since I was already here I started with indoor unit and checked all components, blower cap is in tolerance blower motor in good condition Drain pan had a switch but no moisture present and drain lines had no clogs Lastly I checked deltas and had 19° of cooling Moved to outdoor and found compressor saver kit indicator bubble was popped but after checking LRA draw it was only slightly above rated amount Capacitor was in tolerance and contactor was in good condition I reviewed with homeowner and recommended compressor saver replacement Homeowner is going to hold off for now but I let her know if issue arrives again to have us come back out and we can see if there is another issue besides compressor saver. System left on cooling upon departure