For this evaluation the condenser was showing an L2 Fault "HPCO Lockout". I reset the board and gauged up where the high side pressure was only getting to around 350 PSI and holding steady, not close enough or over to trip High Pressure cut off. I ran the twice and both times the system reach temperature with the same result not hitting head pressure. I disconnected the high pressure cut off switch on the board and use the jumper to close that circuit and bypass the high pressure cut off switch.