On arrival system was running and cooling producing a 19 degree delta. Indoor unit was very clean and the drain line flowed when flushed. Outdoor units capicator was out of tolerance and the compressor overamped on start up. I installed a new capicator and a hard start kit to remedy this. When I left system was running and cooling