1412 Greenwood Road
Weatherford, TX 76008
817-596-4808

Our Top Cities


Job Locations
for trophy club, tx


Map of Trophy Club TX
wade.gordzelik@acgenius.com

wade.gordzelik@acgenius.com


Job Checkin

For this evaluation the customer system was not cooling because the compressor wasn't thermal lockout because the fan side of the Dual run capacitor was completely dead therefore the fan was not running causing the compressor to overheat. That sure changed out the capacitor and drench the compressor and water to allow it to cool off the system however the call was being interrupted by the low pressure switch because his system was low on refrigerant. I like search the evaporator coil where I did get positive indications of refrigerant indicating the leak was in the evaporator coil. Due to the age of the system and the price of refrigerant the customer decided to talk with a comfort advisor schedule for Monday the 16th.