7/18/23 Arrived for service eval System low on refrigerant Leak found at condenser field weld Pump down Welded hole closed Pressure test with bubbles - no leaks present Pulled vacuum to 500 10 min decay test Refilled system Will return tomorrow to check charge and finish adding refrigerant - tank ran empty before ideal levels were reached