Came to visit with system down. Furnace disconnect switch had surge hit and was burned and not giving correct voltage to unit. Replaced disconnect and system is in working order. Both system inside blowers and coils are good. System 1 needs duct clean and blower clean. System 2 drain pan is corroded. Talked to customer about drain switches and new drain pan. Outside unit amp draws are within ranges. Capacitor tolerances in range. Cleaned both outside coils. Both systems left in working order