On arrival system was off. I determined that the indoor unit was blowing a fuse due to a burnt relay. I replaced the relay and installed a customer provided thermostat and the system ran and cooled. I inspected the outdoor unit and found the capicator incorrectly wires, the contactor was pitted and the compressor was overamping on start up. I re wired the capicator and installed a contactor and compressor saver kit. When I left the system was running and cooling. Thanks for choosing comfort experts and have a great day!