Tech arrived at a membership package unit tune-up. It was raining. Upon inspection, the capacitor tested out of tolerance. The contactor was in working condition. The system did not appear to have Surge Protection. The filter was recently replaced. The blower area had growth present including in the wiring. The blower wheel was dirty. The drain was clear and bleach was poured. The customer was informed of recommendations today. He decided to move forward with replacing the capacitor. This item was replaced tested and functional. The system was returned to the office position upon departure.