1412 Greenwood Road
Weatherford, TX 76008
817-596-4808

Our Top Cities


Job Locations
for weatherford, tx


Map of Weatherford TX
Ian C.

Ian C.


Job Checkin

4/16/24 Upon arrival I found two control boards with fault codes and two compressors not operating out of 4. One fault code showed open start circuit, located a bad capacitor and swapped 40mfd capacitor. On the other control board I had a faulty outdoor ambient temperature sensor code, located ambient sensor that was caked in sut, cleaned sensor and checked resistance. Sensor was acceptable after cleaning. Reset board and compressor started right up, board did not send code again. While working on condensers I noticed all three systems would cycle on and off every 10-15 mins, checked air handlers and found three emergency drain pans full of water. Systems kept short cycling due to float switch activation. Cleaned emergency drain pans and put condesate treatments in evaporator coil drain pans. All three primary drains were severely clogged, cleared drains and then poured a gallon of water down them. Drains are draining properly now. Systems were no longer short cycling CONDENSERs outsid