Arrived for safety check x3 at 10:15 All three units are missing water safeties and drip legs<br> - recommended to prevent water damage and gas valve failure<br> Upstairs furnace unit has biological growth in the coil drain pan<br> - UV system recommended to improve air quality and prevent spread to ductwork<br> All three units are mildly dusty<br> - cleaning recommended for air quality improvement and lifespan extension<br> Master bedroom condenser should have a hard start kit installed to lower amp draw to compressor to manufacturer specs <br> Downstairs condenser <br> - fan motor is over amping<br> - rated 1.2 amps measured 1.42 amps<br> - - 1/4hp 825 rpms<br> - dual run capacitor needs to be replaced<br> - rated 45/7.5 tested .003/3.1<br> Upstairs condenser<br> - fan motor is rated .5 and measured .58<br> - - 1/12 hp 800 rpms Will follow up next week to determine what work to scheduled