On arrival both systems were running and heating producing 20 degree deltas. The indoor units had clean blowers and coils and the drain lines flowed when flushed. Both outdoor units had weak capicators and one outdoor unit was overamping on start up. I added a capicator and compressor saver kit but need to return to add the other capicator. Please schedule me to return Thursday with the capicator.