Upon arrival both systems were running. The indoor had a 22 degree delta. I recommended a coil cleaning, a blower cleaning, a uv system to kill the biological growth, and a blower capicator to replace the out of tolerance existing one. The outdoor unit was in good shape, the main concern was the compressor amps on start up were at 94 and the maximum the system is rated for is 79. I recommended a compressor saver kit to remedy this. As I left I ensured that both the indoor and outdoor unit were running and cooling effectively. Thanks for choosing comfort experts and have a great day!